System effect of a fan refers to the effect on the duct system.
It has to do with the amount of air and pressure that a real fan can deliver when working with real pipes.
It is not a value measured from the fan curve alone.
🔹 Principles
• Fans are tested at the factory under standard conditions assuming “ideal” duct connections.
• But when actually installed, there are often imperfections such as
• There is no straight pipe before entering the fan (Inlet Condition).
• There is no straight pipe behind the fan (Outlet Condition).
• There is an obstructing device such as Elbow, Damper, Transition too close to the fan.
This will cause a System Effect Factor (SEF) = additional pressure loss not covered by the Fan Curve.
🔹 Impact
1. Extra Static Pressure Loss
→ The fan must work harder. But the actual air came out less than designed.
2. Reduced Airflow, CFM.
→ Because the Fan Curve will “move down” from the tested value.
3. Noise & Vibration (Noise & Vibration)
→ Because the air flow is not smooth and turbulence occurs near the fan.
🔹 How to prevent
• Install Straight Duct before and after the fan according to standards ( / recommended)
• Inlet: Length ≥ 2–3 times Hydraulic Diameter.
• Outlet: Length ≥ 3–5 times Hydraulic Diameter.
• Use Bellmouth, Guide vane to help adjust flow.
• Avoid placing Elbow, Damper near the fan.
• In the calculation, the SEF value must be added to the External Static Pressure (ESP) of the fan.
🔹 Short summary
System Effect = “extra” pressure loss caused by incorrect fan installation → causing CFM
Less true than what the Fan Curve says → Must be considered in design.
Browse the category to compare fan and blower types and models for your application.
View fans and blowers