Procedure for measuring ESP (External Static Pressure) at Fan In / Fan Out
🔹 Step 1 : Prepare equipment
• Manometer / Differential Pressure Gauge
• Static Pressure Probe or Pitot Tube.
• Hose + pipe plug
🔹 Step 2 : Select the measurement position for Fan In (suction side).
• Measure at the air duct before entering the fan.
• Suitable distance ≈ 1–2D from Inlet.
• The pressure value will be negative (–).
🔹 Step 3 : Select the Fan Out measurement position (supply side).
• Measure at the air duct behind the fan.
• Optimal distance ≈ 2–3D from Outlet.
• The pressure value will be positive (+).
🔹 Step 4 : How to measure and read values
• Drill pipe holes Ø6–8 mm
• Insert the probe perpendicular to the wind direction.
• Zero gauge before measuring.
• Save the value.
• SP_in = –xxx Pa
• SP_out = +yyy Pa
🔹 Step 5 : Calculate the actual ESP value\boxed{ESP = |SP_{in}| + |SP_{out}|}
Example in the picture
• SP_in = –120 Pa
• SP_out = +380 Pa
👉 ESP = 500 Pa
📌 Short memories for teaching/work
🔹 Measure static pressure before Fan + after Fan.
🔹 Do not measure on the fan.
🔹 Add the absolute values together = true ESP.Click here to type a system message.